Liquid-Cooled Sodium-Ion ESS Cabinet — 200 kW / 199.68 kWh
All-in-one C&I liquid-cooled sodium-ion outdoor cabinet with 200 kWh battery and 2 × 100 kW PCS. Peak shaving, grid-tied and off-grid operation, pack-level and cluster-level fire protection in an IP54 enclosure.
Key functions
- Peak shaving & valley filling with EMS power-tracking control
- Grid-tied and off-grid operation; supports PV integration
- Pack-level + cluster-level aerosol fire protection (GB/T 42288)
- Smart liquid cooling, 6 kW chiller, -25 ~ +55 °C operation
- Flexible expansion — modular PCS / DC-DC, parallel-ready
- Remote monitoring via Ethernet / RS485, Modbus TCP / RTU
Product gallery



Technical specifications
| Battery type | Sodium-ion, NFPP 3.2 V / 160 Ah cells, 1P416S |
|---|---|
| Rated energy | 199.68 kWh |
| Nominal voltage | DC 1,248 V (748.8 – 1,435.2 V) |
| Rated power | 2 × 100 kW PCS, AC 400 V / 50 Hz, three-phase four-wire |
| DC/DC | 2 × 100 kW, max efficiency ≥ 99%, transfer < 20 ms |
| Overload capability | 1.1 × continuous, 1.2 × 1 min |
| Conversion efficiency | ≥ 92% (system) |
| Cycle life | ≥ 3,000 cycles @ 0.8P |
| Cooling | Liquid cooling, 6 kW chiller, R410A |
| Fire safety | Pack-level + cluster-level aerosol (GB/T 42288) |
| Working environment | -25 ~ +55 °C (derating > 45 °C), 0 – 95% RH, ≤ 2,000 m altitude |
| Communication | Ethernet / RS485, Modbus TCP / Modbus RTU |
| Protection rating | IP54 |
| Weight | approx. 3,200 kg |
| Dimensions (D × W × H) | 1,650 × 1,375 × 2,450 mm |
| Standards | GB/T 36276, GB/T 34120, GB/T 34131, UN38.3, IEC 62619, CE-EMC |
Open the full technical datasheet (PDF) for complete electrical ratings, drawings and certification details.
Questions before you order
Does a rated 199.68 kWh guarantee usable backup duration?
No. Usable capacity depends on the load profile, depth-of-discharge settings, auxiliary consumption, conversion efficiency and reserve requirements. Send your load profile so we can size the energy and PCS together.
Is the cabinet suitable for cold-climate sites?
Yes. The smart liquid-cooling system supports -25 ~ +55 °C operation, with derating above 45 °C. Confirm the local grid voltage, frequency and interface requirements for the final configuration.
Discuss your battery requirements
Send the application, required specifications, quantity and destination for a model-specific proposal and lead time.
Request a quote